The jumper settings for the analog input configurations are as follows:

Input Type

Jumper 1

Jumper 2

0-20mA

2a-2b

3a-4a

0-1mA

1a-2a

3a-3b

0-500uA

1a-2a

4a-4b

0-10VDC

1a-2a

4b-5b

0-5VDC

1a-2a

3a-4a

Sensor Power

Jumper 3

Jumper 4

18V Switched

7a-8a

9a-9b

12V Switched

7a-7b

9a-9b

5V Switched

6a-7a

9a-9b

12V Continuous

7a-8a

8b-9b

Digital Inputs

Up to 3 digital inputs are available that can be configured in any combination of

accumulators (rain gauges, flow sensors) or status inputs (doors switches, power

failure). These inputs can also be programmed to initiate a transmission on any

change of state (event), a door opening or a pump turning on for example. All input

configurations are factory programmable only.

The quick-connect input connectors are color coded for easy wiring. Black terminals

are connected to ground, red terminals are connected to 12VDC continuously, and

the digital inputs are colored white. Insert the wire into the connector and push the

locking lever down. To release the wire, lift the lever up until it locks it place.

The digital inputs have 20Kohm pull-up resistors to the +5volt internal power supply

of the circuit board. This input is intended to be switched to ground only, either by a

switch contact closure or by a switching transistor. Driving these inputs with a

positive voltage other than 5volts can result in excess current drain and improper

circuit operation.