DTP HDMI 230 D Transmitter and Receiver • Installation and Operation

10

Connector and Cable Details

TP Cable Termination and Recommendations

Figure 9 details the recommended termination of both ends of TP cables with RJ-45
connectors in accordance with the

TIA/EIA T 568B wiring standard.

5

Pin

1

2
3

6
7
8

4

Wire color

White-green

Green

White-orange

White-blue

Orange

White-brown

Brown

Blue

TIA/EIA T

568 B

TP Wires

12345678

Pins:

Figure 9.

TP Cable Termination

NOTE: Do not use Extron UTP23SF-4 Enhanced Skew-Free AV UTP cable or STP201

cable to link the transmitter and receiver. The DTP HDMI 230 D Tx/Rx does not work
properly with these cables.

Supported cables —
The DTP HDMI 230 D is compatible with CAT 5e, 6, 6a, and 7 shielded twisted pair (F/UTP,
SF/UTP, and S/FTP) and unshielded twisted pair (U/UTP) cable.

Cable recommendations —
Extron recommends using the following practices to achieve full transmission distances up
to 230 feet (70 m) and reduce transmission errors.

•

Use the following Extron XTP DTP 24 SF/UTP cables and DTP 24 connectors for the
best performance:

•

XTP DTP 24/1000

Non-Plenum 1000’ (305 m) spool

22-236-03

•

XTP DTP 24P/1000 Plenum 1000’ (305 m) spool

22-235-03

•

XTP DTP 24 Plug

Package of 10

101-005-02

•

If not using XTP DTP 24 cable, at a minimum, Extron recommends 24 AWG, solid
conductor, STP cable with a minimum bandwidth of 400 MHz.

•

Terminate cables with shielded connectors to the TIA/EIA T 568 B standard.

•

Use no more than two pass-through points, which may include patch points, punch
down connectors, couplers, and power injectors. If these pass-through points are
required, use CAT 6 or 6a shielded couplers and punch down connectors.

NOTE: When using CAT 5e and CAT 6 cable in bundles or conduits, consider the

following:

•

Do not exceed 40% fill capacity in conduits.

•

Do not comb the cable for the first 20 meters, where cables are straightened,
aligned, and secured in tight bundles.

•

Loosely place cables and limit the use of tie wraps or Velcro

®

.

•

Separate twisted pair cables from AC power cables.