OM-06331

SUPER T SERIES

OPERATION

PAGE C - 4

put contacts close, then after the “Hrn dLy”
time, A output contacts close. A output con­
tacts will remain closed as long as Low Tem­
perature Thermostat contacts are closed.

When the Low Temperature Contacts open, A
output contact will open only if the level is
equal to or less than the “A.off” setpoint.

As long a the Low Temperature Thermostat
contacts are closed, the display will show “lo

tpt” unless

switch is pressed to display

some other information. Level is not viewable
until the Low Temperature Thermostat con­
tacts open.

The user may wish to check Setpoints Off/On
and Horn output/A output delay times. “Bump­

ing” the

switch will display all of the informa­

tion desired.

NOTE

One second delays in contact opening/closing is a
result of time sampling of the pressure signal to fil­
ter false signals that could cause “nuisance” trip­
ping of the contacts.

NOTE

If the “Hrn dLy” is changed during the actual A out­
put delay cycle, the current cycle is not changed;
the change becomes effective on the next A output
delay cycle.

Use caution to ensure that the “‐‐.on” set­
point (i.e. “A.on”) is not adjusted to a level
less than the corresponding “‐‐.of” set­
point (i.e. “A.of”). Improper adjustment of
the off/on setpoints will render the unit non‐
functional, resulting in flooding.

EPS Calibration

NOTE

Zero offset and span adjustments are only neces­
sary to calibrate a new unit, or when replacing the
transducer. Once calibrated, “ON” and “OFF” set­
points will be stored in the unit's memory. Liquid

level adjustments will be used whenever “ON” and
“OFF” liquid levels must be reset.

There are two reasons for the user to calibrate the
unit. When power is applied, the unit confirms set­
points and other calibration information for validity.
If the setpoints are not valid, the LCD screen shows
“EEP bAd” and the unit must be recalibrated. Also,
if the unit is moved, or some other external change
takes place, the unit must be recalibrated.

Zero Adjustment

Zero adjustment tells the unit when the transducer
is exposed to zero water (atmospheric) pressure.
When recalibration is desired, hold the transducer
in hand and apply power to the unit. The LCD

screen will display “Level ABC”. Press and hold
for 5 seconds. The LCD screen displays “Input?
External XDUCR”. Perform the following calibration
procedures.

Press

3 times and the LCD screen will display

“Calibrate Zro”. Press

or

until a character or

number on the display changes.

Press

to accept the entry and advance to “Cali­

brate Span”.

Span Adjustment

Span adjustment calibrates the unit to a known wa­
ter pressure (depth). To set:

Submerge the transducer to an exact known
depth. At “Calibrate Span”, the span setting in the

unit's memory will display. Press

to increase or

to decrease the value unitl the LCD screen dis­

play equals the actual known depth of the trans­
ducer.

Level Adjustment

Level adjustment tells the unit when to turn the
pump on and off. To set:

From “Level ABC” display, press

once and

“Pump Setpt A On” will display. Press

to in­

crease or

to decrease to the desired level at

which the pump turns on. Press

to advance to