Radon Installation

IMPORTANT: All installations in Radon environments should be done by a qualified professional and in accordance with

applicable codes.


A. The access cover must seat against the secure cover to ensure the gaskets provide a sealed gas-tight system (see fig. 5).

Additionally, ensure that the gaskets between the covers create a seal.

B. Install a 3” vent line at the cover connection labeled “OPTIONAL RADON VENT LOCATION”. Use a 4” hole saw to create a hole

in this location. A dimple is provided on the cover to properly center the drill (see figure 4, above). Install the provided 3” pipe seal

in the hole. Place 3” PVC vent pipe from the vent system through the pipe seal. Do not place the vent pipe more than 4” into the

basin.


Fig. 4 Finish plumbing, wiring and switch locations

Optional radon vent location (see

Radon Installation section). Use a 4”

hole saw to open the hole. The dimple

serves as a center mark for drilling.

1-1/2” threaded

discharge location.

Optional alarm

switch cord

grommet.

Optional alarm

switch.

Pump power

and switch cord

grommet.

Pump switch.

Fig. 5 Correct Access Cover Installation

There should be

no gap between

covers for the best

possible seal.

Secure Cover

Access Cover

Gasket tape should

contact access

cover in this area