Commissioning
The base settings are now completed and the drive can be started:
Start drive
Note
Enter the setpoint.
A) Using the keypad
Set desired output frequency
under C0140.
The min. frequency under
C0010 and the setpoint offset
under C0140 are added!
B) Using the potentiometer via terminals 7, 8,
9
Terminal
E3 E4
34 Hz (2000/min)
HIGH
LOW
67 Hz (4000/min)
LOW
HIGH
12.
C) Enter fixed speed via terminal.
50 Hz (3000/min)
HIGH
HIGH
13. Enable controller.
misc002
Terminal X3/28 = HIGH
14. The drive now operates with the set
frequency. The current output frequency is
indicated under C0050.
Set Disp
SubCode Para H / L
If the drive does not start, press
in addition.
5.4
Shut-down of the pump-motor unit
Shut-down:
1 Set controller inhibit (terminal X3/28 = LOW)
2 Switch off power supply.
3 Close shut-off device in inlet/ pressure line.