Default function

I1

»RUN«. Integrated pull-up resistor. Pump stops when input is connected to 0V.

I2

»MAX«. Pump will start to operate with maximum power if logical “1” (24V) is

detected.

5.3

24V

supply

Output is meant for automation elements.

Electrical properties

Maximum current

up to 100mA

Output voltage

24V ±20%

Output ripple

under 1V

Misconnection or overload could cause pump shutdown or even permanent

damage.

5.4

r

elay

ouTpuT

relay output

Rated current

8A

Maximum voltage

250VAC

48VDC

Maximum load

up to 500VA

Default function

ALARM »error«

5.5

e

TherneT

specifications

Connector

RJ-45

Speed

BASE-10, 10Mbit/s

Galvanic insulation

To digital inputs: 1.5kV@1s, 48V permanent
To line voltage: 4kV@1s, 275V permanent

Connection

TCP/IP

Services

http server and client, FTP server

Web language

HTML 1.1

5.5.1

s

earch

Of

a

lOst

pump

If you have forgotten IP address or NetBIOS name or if you accidently set it to an

incorrect value, pump can still be found with network analyzers. Freware tools like

»WireShark« or »EtherDetect« can help you to trace the pump as it periodically

tries to contact its twin. This is true even in the case of single pump. You can trace out the device

that sends out requests and contact it directly.