General Information

The T5 Series console* with an internal TS-DIMIB Dispenser

Interface Module has built in diagnostic software which

enables an installer to verify communication with the

dispenser / POS system.. This is a menu-based command

line utility which is available through the serial port of the

Power Supply Module. Control Module Firmware version

0.9.5.3685 or greater is required and Power Supply Firmware

version 1.0.1 or greater is required.
Prior to using diagnostic mode
Note
: If the console is not communicating with the

Distribution Box (Dbox), verify that the modules are

at the most current rev. level. If needed, upgrade the

system to current revs, turn off power to the T5 series

console, wait 5 minutes and turn power back on.

Note: If the mapping query is not working, set all hose

positions in set-up to 0 and save configuration.

Check status of the DIM module and wait until the

console shows the DIM is operational. Return to

setup and query dispenser.

In order to use this diagnostic, the console will need to

be placed into an offline mode which essentially turns the

power supply into a dedicated module for DIM diagnostic

use only. During this time, the T5 console will not be

performing normal operational functions.
To return the console to its normal operation mode, it will

need to be power-cycled. This will allow the Power Supply

to return to its normal state. Note a Power Supply Module

Mismatch alarm will occur and should be ignored.

Procedure

Step 1

Using the LCD panel, select the main menu: FMS (Figure 1).

Figure 1: LCD Home Screen

This will take you to the Menu page. Press the DOWN

button (Figure 2).

Figure 2: Main Menu

This will show the diagnostics screen (Figure 3).

Figure 3: Diagnostics Button

TS-DIMIB Diagnostics

*T5 Consoles include TS-5, TS-550, TS-5000 and TS-EMS