Franklin Fueling Systems TS-DIMIB Diagnostics User Manual

Page 2

Advertising
background image

2

Select the DIM Diagnostic in the Diagnostics section of the

Main Menu (Figure 4).

Figure 4: Diagnostics Screen

Once selected you will be prompted to confirm your

selection (Figure 5).

Figure 5: Confirmation Screen

Select OK and you will be prompted to enter the

Administrator password. Enter the password and select the

check box Figure 6).

Figure 6: Password Screen

The system will now enter DIM Diagnostic Mode (Figure 7).

Figure 7: Diagnostic Mode

Step 2

Connect to the console via an Ethernet connection,

and reboot the system (soft boot) by choosing

tools \ reboot system.
Using a NULL modem cable connect COM Port 2 of the T5

series console to a COM port on a PC.

A

B

GND

+

-

TPI RS-485

COMM2

BUS EXT

FAX/MODEM

COMM 1

ETHERNET

USB

H

CURRENT LOOP

RS422/232

Figure 8: T5 Console COM Port 2 Location

Open a terminal emulator program (e.g. Hyper Terminal) with

protocol setting of 57600 Baud, 8 Data Bits, No Parity, and 1

Stop Bit (Figure 9-11).

Figure 9: Terminal Program Open