3.3 AlphaCell
TM
Battery Maintenance Log
Follow this sample when filling out the maintenance log (following page).
Evaluation Procedure
#1
Evaluation Procedure
#2
Evaluation Procedure
#3
Vdc
Float
No
Load
Conductance
mhos @
77°F
Vdc 24
Hour
OCV
Conductance
mhos @
77°F/25°C
Vdc @
100A after
10 seconds
Vdc 24
Hour
OCV
A
1
195GxL
4/08
3/08
.2
70°
13.4
1100
A
2
195GxL
4/08
3/08
.2
70°
13.5
1080
A
3
195GxL
4/08
3/08
.2
70°
13.4
1120
B
1
195GxL
4/08
3/08
.1
70°
13.4
1090
B
2
195GxL
4/08
3/08
.1
70°
13.4
1105
B
3
195GxL
4/08
3/08
.1
70°
13.6
1060
A
1
195GxL
4/08
3/08
7/8
.1
85°
13.3
1120
A
2
195GxL
3/08
7/8
.1
85°
13.3
1100
A
3
195GxL
3/08
7/8
.1
85°
13.4
1105
B
1
195GxL
3/08
7/8
.1
85°
13.2.
1070
B
2
195GxL
3/08
7/8
.1
85°
13.2
1100
B
3
195GxL
3/08
7/8
.1
85°
13.2
1080
String
Battery
Type
Battery
Initial Install Date
Mfr
. Date Code
PM Date Float Current
Battery
Temp
Node / Location
Power Supply Type
Load (kW)