Battery symptoms and solutions, 0 battery symptoms and solutions, continued – Alpha Technologies AlphaCell GelCell Series User Manual

Page 23

Advertising
background image

23

745-680-C0-002, Rev. B

5.0

Battery Symptoms and Solutions, continued

Problem with

Symptom

Possible Causes

Possible Result

Corrective Actions

DC Voltage

Checks

System float voltage >

2.3V/C average 77°F

(25°C)

Charger output set

incorrectly

Overcharging causes

excessive gassing and

drying out of electrolyte

and contributes to potential

thermal runaway.

Reset the charger output

voltage to recommended

value.

System float voltage <

2.25V/C average 77°F

(25°C)

Charger output set

incorrectly

Undercharging results in

gradual loss of operating

time and capacity with

successive discharge cycles.

If persistant, an irreversible

level of lead sulfate develops

on the plates resulting in a

permanent capacity loss

Reset the charger

•

output voltage to

recommended value.

Equalize battery system

•

from 48 to 72 hours

and perform capacity

test. If capacity loss is

permanent, replace the

total battery system.

Individual battery float

voltage > 13.3 VDC

Potentially the

•

individual battery has

shorted cell

Verify with impedance

•

or conductance check

Reduced operating time

under load. Increased float

current. Heating of cell during

discharge. Contributes to

potential thermal runaway.

Replace individual battery.

Individual battery float

voltage 14.5 VDC for

6 cell

Potentially open cells in

individual battery. Confirm

by checking for zero float

current or check for very

high impedance of the

battery.

Failure to support load. Could

result in an internal arc, could

ignite gasses within the cell.

Replace individual battery.

DC voltage measured

between battery system

output terminals and

ground (rack) or a

ground fault indicated

by automatic monitoring

equipment.

Damaged container allow-

ing electrolyte to wick out

to grounded surface (rack).

Personnel shock hazard

•

resulting in serious

injury or electrocution.

Potential burning of

•

container at damaged

area or battery fire.

Determine the source of

ground fault and replace

battery.

Temperature

Checks

Elevated room tem-

perature

Lack of adequate air condi-

tioning or ventilation

Reduced battery life

Cool room or accept reduced

battery life

Elevated battery temp.

Elevated room temp.

•

Inadequate cabinet

•

ventilation

Discharge - charge

•

cycle

Reduced battery life

•

Reduced life and

•

potential thermal

runaway

Normal if not exceeding

•

18°F increase

Improve room air

•

conditioning

Improve cabinet

•

ventilation

Limit recharge current

•

High current recharge

High charging voltage

•

Shorted cells

•

Normal if not exceeding

18F/10C increase over

ambient

Limit recharge current

•

Reduce within

•

specifications

Replace shorted cells

•

and evaluate total string.

Table 2, Battery Symptoms and Solutions, continued