5.7.2

Battery Connections

There are connection points for two strings of batteries. Use the thumbscrew lock to disengage part of the

distribution assembly and slide it out the right side of the shelf as far as necessary (Figure 9).
Connect the battery (+) cabling to the bottom set of studs and the battery (–) cabling to the upper set. Lugs

required are 1/4" on 5/8" centers. Refer also to Figure 9a with respect to the battery cables and the

connection points positioned for proper access.

5.7.3

Breaker Ground Connections

The load breaker returns (+) for each of the four breakers are also found on the same part of the (sliding)

distribution assembly.
Connect to the breaker (ground) returns using 1/4" on 5/8" center lugs.
Slide the connection point assembly back into the distribution module and secure with the thumbscrew lock

(Figure 10). Note the cable(s) and the connection points positioned for proper access.

A Philips or slotted head screwdriver may be needed to secure the thumbscrew lock

Figure 10–Breaker ground connections

Thumbscrew

lock

Load breaker

return (+) 4PL