Specifications for Argus Technologies’ FMPS Continued

Argus Technologies Ltd.

010-592-B1 Rev A WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 5

Local Alarms

System LED:

Green steady = system output normal, DC output/off = no AC or battery power


Battery LED:

Yellow steady = system on battery/off = normal mode


Replace Battery:

Red steady = replace one or two battery strings/off = batteries within parameters


Replace Battery A&B (internal): Red steady = replace one or both battery strings/off = batteries within parameters

Audible Indicator (Alarm On):

Alarm enable/disable toggle switch located on FMPS, batteries below voltage
parameters


Remote Alarms

SEE ALSO CONNECTIONS
Pin 1 Alarm Return:

Open collector return reference


Pin 2 AC Fail:

On battery


Pin 3 Replace Battery:

One or both battery strings failed periodic self-test


Pin 4 Missing Battery:

< 8 batteries


Pin 5 Battery Low:

Battery string voltage < 46.8Vdc


Connections

Output:

2x terminal blocks accepting #16 AWG (1.5mm²), parallel connections


Remote Alarms:

2x 5-position IDC #24 AWG (0.25mm²), parallel connections


Mechanical

Dimensions

FMPS:

603mm H x 356mm W x 140mm D
(23.75” H x 14” W x 5.5” D)

FMPS + Shipping Carton:

724mm H x 432mm W x 298mm D
(28.5” H x 17” W x 11.75” D)


Weight

FMPS: 11.3

kg

(25 lb.)

FMPS + Shipping Carton:

13.6 kg
(30 lb.)


Battery

Type:

4 or 8 7.2AH valve regulated lead acid (VRLA)


Model:

GS Battery Inc., OEM P/N: PX12072F2-HG
CSB, OEM P/N: GP1272F2

For compatibility with other battery models, please consult Argus factory.