Alpha Technologies Micro, Micro XL, Micro XL3 UPS User Manual
Page 24

017-237-B0 Rev A
22
Remove knockouts as needed.
Install conduits if used.
Secure wiring to
backing plate with
tie wraps.
Alternate routing for
output wiring.
Push button down to insert wires
into terminal block
Figure 15 — Wiring the Alpha Micro
The input and output wiring must NOT touch the cabinet except for the wiring manage-
ment panel.
Each terminal block has two inputs for each pole (line, neutral and ground). Make sure
you have inserted each wire into the correct position and not accidentally connected the
line and neutral to the same pole.
Verify the line wire is attached to the line terminal block, the ground wire is attached to
the ground terminal block and the neutral wire is attached to the neutral terminal block
to prevent accidental shocks or electrocutions.
WARNING!
6. Secure the wiring to the wiring management panel with tie-wraps provided with the Alpha Micro. Make sure
that the wiring is long enough to reach the terminal blocks.