11 hvac default settings – Alpha Technologies Te41, 48V User Manual
Page 36

Argus Technologies Ltd.
057-102-C0 Rev B WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 25 of 26
11
HVAC Default Settings
Refer to the air conditioner manual (supplied with the system) for operation and maintenance details.
11.1 Air Conditioner/Heater Package
Description Setting
Cooling System ON Temperature
80
qF [26.6qC]
Heating System ON Temperature
60
qF [15.5qC]
HVAC Fail Alarm
(e.g. by dirty filter or failed condensor)
300psi, reset at 225psi
11.2 Enclosure
Temperature
Alarms
Battery Compartment Thermostat
Setting
High Temperature Alarm (Blue)
35
qC (95qF)
Low Temperature Alarm (Red)
-15
qC (5qF)
Power Compartment Thermostat
Setting
High Temperature Alarm (Blue)
65
qC (149qF)
Low Temperature Alarm (Red)
-15
qC (5qF)
11.3 Cooling
Fans
Fan speed is controlled electronically. At temperatures below 30
qC (86qF) they will shut off.