11

Factory Ranges and Defaults

Submenu Item

Programmable Range

Default Setting

12Vdc

24Vdc

48Vdc

125Vdc

220Vdc

Float (FL) Voltage

0-9999999999

13.50V 27.00V 54.00V 130.50V

229.5V

Equalize (EQ) Voltage

0-9999999999

13.75V 27.50V 55.00V 132.92V

233.75V

Battery Test (BT) Voltage

0-9999999999

11.50V 22.00V 44.00V 106.33V

187.00V

OVP 0-9999999999

14.25V

29.00V 57.00V 137.75V

242.25V

LVA 0-9999999999

11.00V

22.00V 44.00V 106.33V

187.00V

HVA 0-9999999999

14.00V

28.00V 55.50V 134.13V

235.88V

Current Limit (CL)

0-9999999999

100%

Power Limit (PL)

0-9999999999

100%

Equalize Timeout

0-9999999999

30 hours

Battery Test Duration

0-9999999999

8.0 hours

Slope (Adjust)

0-9999999999

1.00%

Backlight Timeout

0-32767

1 minute

Security Code

0-32767

123

Module Start Delay

0-32767

1 second

System Start Delay

0-32767

0 seconds

Soft Start Ramp Rate Normal/Fast

Normal

Temp Display Scale

Celsius/Fahrenheit

Celsius

Current/Power Limit Alarm

Enable/Disable

Disable

Remote Shutdown

Enable/Disable

Enable

Local Access Alarm

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

Power Save

Enable/Disable

Disable

Redundant Rectifiers

0-32767

1

Maximum Power Usage

0-32767

80%

Table E–Rectifiers menu defaults

Submenu Item

Programmable Range

Default Setting

Load Voltage (V1)

Decimal precision: 0-3

2

Load Current (I1)

Decimal precision: 0-3

1

Battery Voltage (V2)

Decimal precision: 0-3

2

Battery Current (I2)

Decimal precision: 0-3

1

AC Mains

Decimal precision: 0-3

1

Battery Temperature

Decimal precision: 0-3

2

Temp Comp Sensor 1

Enable/Disable

Disable

Temp Comp Sensor 2

Enable/Disable

Disable

Temp Comp Sensor 3 (GP1)

Enable/Disable

Disable

Temp Comp Sensor 4 (GP2)

Enable/Disable

Disable

Battery Runtime

Decimal precision: 0-3

2

Battery Capacity

Decimal precision: 0-3

1

Battery Depth of Discharge (DOD)

Decimal precision: 0-3

1

Analog Inputs

See 6.6.1.1

N/A

Digital Inputs (1-8)

High/Low

Low

Rectifier Signals

See Menu Tree

N/A

Custom Signals (1-10)

Decimal precision: 0-3

2

Signal Units (1-10)

A, V, W,

C (F)

V

Table F–Signals menu defaults