3 CXCM

Features

The CXCM (Cordex Controller, Modular) is mounted in the rectifier system shelf and brings advanced monitoring
technology to the Cordex series of rectifiers. This compact 4RU system controller is designed for seamless
operation and set up of Argus power systems and is equipped with the complete range of Cordex software
features, including the following:

• Designed to communicate directly with Cordex rectifiers

• Includes battery temperature compensation charging

• Battery performance diagnostics

• Provides local and remote communications

• User definable alarms

• Daily logging of power system events and system statistics.

Behind the CXCM’s front panel lies the main controller motherboard, which contains a microprocessor, memory,
as well as numerous other electronic components.

The CXCM includes a web server providing easy set up and monitoring using an Internet connection with the
standard Windows® Internet Explorer browser.

The data logging feature allows the user to capture data from multiple inputs, for AC/DC voltages, load/battery
current, cell voltages & temperatures (automatically for up to 16 user defined logs). Typical applications of the
CXCM logging include power system details, thermal performance of outdoor enclosures, battery cell specifics, or
mains variations captured by an AC voltage watchdog.

A built-in audio speaker sounds an intermittent tone during active alarms.

The input/output (I/O) board houses a series of terminal connections; located at the back of the system shelf.

3.1 Front

Panel

3.1.1 Display

Located on the front panel is a 160 x 160-pixel graphical LCD with touch screen similar to those used in PDAs.
This graphical user interface (GUI) allows the operator to interact with screen selectable items using a fingertip.

Figure 3–Cordex CXCM model system controller front panel

Touch screen

Reset (RST) button

RS-232 (craft port)

System status LEDs