7.4

Factory Ranges and Defaults

The following table lists the rectifier settings/ranges/defaults; changes are made via the CXC:

Setting

Range (minimum to maximum)

Default

Float Voltage

47.5 – 58.2V

54V

Equalize Voltage

49.8 – 60.2V

55V

Battery Test Voltage

44 – 52V

46V

OVP

See note below – 63V

57V

Current Limit

23 – 100%

100%

Power Limit

0 – 100%

100%

Module Start Delay

0 – 250s

1s

System Start Delay

0 – 600s

0s

Low Voltage Alarm

42 – 52V

44V

High Voltage Alarm

52 – 63V

55.5V

Equalize Timeout

1 – 2399h

30h

Battery Test Timeout

1 – 250h

8h

Softstart Ramp-rate

Normal/Fast Normal

CL/PL Alarm

Enable/Disable

Enable

Remote Shutdown

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

Table E–Cordex 48-1kW Rectifier factory ranges and defaults


NOTE: OVP cannot be set below the present system voltage, float voltage setting, equalize voltage setting, battery test

voltage setting or the safe mode voltage of 51.4V.