0 local port – Alpha Technologies DOCSIS HMS User Manual
Page 17

17
745-420-C0-002 Rev. B
Battery
Input
Temp
Probe
Battery
Breaker
LOCAL
RF
RS-232
port
Local port
Laptop Computer
With
HyperTerminal
(19,200,8,N,1)
Logic Level
Converter
Alpha P/N 875-349-10
4.0 Local Port
The local port allows the technician to communicate with the transponder and power supply through a
PC’s RS-232C serial port.
1.
Connect the optional Local Port to RS-232C Adaptor Cable (Alpha P/N 875-349-10) between the
transponder’s Local Port and the computer’s serial port. Launch the computer’s Terminal Emulation
Software (HyperTerminal is recommended).
Fig. 4-1, Local Port to PC Connection
2.
Communication settings are:
•
19,200 baud
•
8 data bits
•
No parity bit
•
1 stop bit
•
No flow control
3.
Press ENTER to initiate communications.
4.
Press “?” and ENTER to display the menu:
HELP
- This help
?
- This help
RESET
- Reset transponder
STATUS
- Transponder config and status
ALARMS
- Display active alarms
ID
- Enter logical ID
PSDATA
- Display power supply data
DEVICE
- Display device status
PSTEST
- Initiate power supply test
GENDATA
- Display generator data
GENTEST
- Initiate generator test
GENRESET