0 specifi cations, Hardware, Environmental – Alpha Technologies IDH3 User Manual

Page 26: Rf transmit/receive, Power supply monitored parameters, Generator monitored parameters

Advertising
background image

26

745-420-B0-001 Rev. A

Power Supplies Supported:

XM2-HP, XM2

DOCSIS Compatibility:

DOCSIS 1.1, 2.0

Monitoring Protocol:

SNMP v1

Devices Monitored:

Power Supply, Batteries and Generator
(compatible with ANSI/SCTE 25-3 2002,
formerly HMS 022)

Hardware

RF Cable Interface:

F-connector, female, 75Ohm

Local Interface:

Ethernet interface for direct web page
access to diagnostic information.

LED Indicators:

Transponder Ready/RF Link Established
Transponder/CMTS Communications
Power Supply/Transponder
Communication

Environmental

Operating Temperature:

-40 to 65°C / -40 to 149°F

Humidity:

10 to 90% non-condensing

Emissions:

EN50022 Class A and FCC Part 15
Class A
(Installed in power supply enclosure
system)

RF Transmit/Receive

Tx Frequency Range:

5 to 42MHz

Output Power:

8 to 58dBmV

Channel Bandwidth:

6MHz

Receive Center
Frequency Range:

91 to 857MHz (Standard, HRC, IRC
channels)

Input Level:

-15 to 15dBmV

5.0 Specifi cations

Power Supply Monitored Parameters

Major Alarm:

Logical (OR) of: test fail, battery fail, line
isolation alarm, output overload, inverter
over temperature, N+1 active, fuse fail

Minor Alarm:

Logical (OR) of: temperature probe error,
AC line loss, N+1 error

Input Line Voltage:

90 to 270Vac 50/60Hz measured value

Output Voltage:

60/90Vac measured value

Output Current 1:

0 to 25A measured value

Output Current 2, 3, 4:

0 to 25A measured value (if optional ports
installed)

Output Power:

Calculated, reported in AC Watts

UPS Status:

AC line, Standby, Test in-process, Test
alarm

Enclosure Door:

Open/Closed

Battery Voltage:

6 or 12V batteries, up to 4 battery strings
Individual battery voltages measured
reported to ±100mv resolution

Battery Temperature:

Measured, reported in Celsius

Remote Test Control:

Start/Stop XM2 self test cycle

Generator Monitored Parameters

Status:

Engine off, running, alarm

Generator Alarm:

Aggregate alarm consisting of: low oil
pressure, engine over-temp, engine over-
speed, crank limit, over voltage, low fuel,
water intrusion, pad shear, gas hazard,
test fail

Gas Hazard:

OK, Alarm

Water Intrusion:

OK, Alarm

Pad Shear:

OK, Alarm

Enclosure Door:

Open, Alarm

Ignition Battery Voltage:

10.2 to 15.5Vdc, 100mV resolution

Enclosure Temperature:

-40 to 100°C / -40 to 212°F

Low Fuel:

OK, Alarm

Remote Test:

Start and Stop control input

Advertising