0 start up and verification – Alpha Technologies AlphaNet IDH4 for XM2 and XM2-300HP Series - Technical Manual User Manual
Page 67

67
746-257-B2-001, Rev. B (01/2014)
9.2
Verifying Correct Hardware Interconnection
The BAT A/B and BAT C/D LED indicators on the front panel of the IDH4 Series unit should illuminate
solid green once the battery wiring harnesses are correctly installed.
The IDH4X model provides both BAT A/B and BAT C/D LED indicators and battery harness connectors
(supports a maximum 4 battery strings). The IDH4 model provides only the BAT A/B LED indicator and
battery harness connector (supports a maximum 2 battery strings).
NOTE:
From the HMS Data section of "HMS" tab of the IDH4 Series Web page, the following screen will
be visible and the parameters shown will be available for viewing and verification. To test hardware
interconnection using the Ethernet port, verify valid values for Output Voltage, Output Current and
individual battery voltages.
Fig. 9-2, HMS Tab Screen
9.0 Start Up and Verification