Connector

Pin #

String Reference

Wire Label

NetMentor Display (36V)

A/B

1

1A - (0Vdc)

A/B[C/D] NEG

2

1A + (+12Vdc)

Vbatt 1A [C] 12V

Battery #3 Vdc

3

2A + (+24Vdc)

Vbatt 2A [C] 24V

Battery #2 Vdc

4

3A + (+36Vdc)

Vbatt 3A [C] 36V

Battery #1 Vdc

5

1B + (+12Vdc)

Vbatt 1B [D] 12V

Battery #6 Vdc

6

2B + (+24Vdc)

Vbatt 2B [D] 24V

Battery #5 Vdc

7

3B + (+36Vdc)

Vbatt 3B [D] 36V

Battery #4 Vdc

8

C/D

1

1C - (0Vdc)

A/B[C/D] NEG

2

1C + (+12Vdc)

Vbatt 1A [C] 12V

Battery #9 Vdc

3

2C + (+24Vdc)

Vbatt 2A [C] 24V

Battery #8 Vdc

4

3C + (+36Vdc)

Vbatt 3A [C] 36V

Battery #7 Vdc

5

1D + (+12Vdc)

Vbatt 1A [D] 12V

Battery #12 Vdc

6

1D + (+12Vdc)

Vbatt 2A [D] 24V

Battery #11 Vdc

7

1D + (+12Vdc)

Vbatt 3A [D] 12V

Battery #10 Vdc

8

NOTE:

Only THREE 36V strings can be monitored when
using a generator. DO NOT connect a fourth string
to the BATT C/D connector if using the generator option.

B attery String A

Battery S tring B

12V

24V

36V

12V

24V

36V

12V

24V

36V

12V

24V

36V

B attery String C

Battery String D

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1A

2A

3A

1B

2B

3B

1C

2C

3C

1D

2D

3D

To P ow er Supply

1.3

Battery Monitor Connections

, continued

Figure 1-9 Battery Monitor Connections for four 36Vdc battery packs