Alpha Technologies APX Series User Manual
Page 15

15
016-030-B0-005, Rev. C
2.1.2 Concrete and Steel Poles
Materials Required:
Two (2) 1-1/2" approved mounting straps, length to suit pole.
Tools Required:
Assorted sockets or wrenches
Procedure:
Mark the position for the upper mounting strap on the utility pole.
Run two approved 1-1/2" mounting straps through the mounting bracket located
on the back of the baseplate assembly.
Center the baseplate assembly on the pole and tighten the mounting straps.
Install the Modular Transformer Assembly (MTA) onto the baseplate (see Section
2.8 for details).
1.
2.
3.
4.
2.0 Installation,
continued
2.1
Pole Mount Installations, continued
Fig. 2-1, APX Enclosure Pole Mounting
VSF Output Connector
NOTE: If mounting to a
steel or concrete pole, use
these two strap slots
#8 AWG (Minimum)
Copper Ground Wire
Cable Output
Utility Power Input
(from Service Entrance)
Enclosure Mounting Bracket
5/8" Diameter Bolts and
Associated Hardware
Service Drop
To Service
Entrance
APX Enclosure
4 1/2”
center-center