3.1 USM2 Configuration,

continued

Function Switch SW2 Reference

The following information describes the each switch position (1–4) for the DIP switch SW2. This switch is a four switch

component and is used primarily to select/deselect pull-ups to digital signals for the USM2 card.

SW2 (1): Equipment Fail Alarm Pull-up Select

SW2, position 1 is used to enable or disable the 10k Ohm pull-up to AUX DC on the system’s transponder
“Equipment Fail Alarm” pin #6 of J3.

SW2 (1) Equipment Fail Alarm Pull-up
OFF

Open collector output with no pull-up.

ON

Open collector output with 10k pull-up to AUX DC.

NOTE:

For “Tri-level” alarm (see SW2 (2) below), SW2 (1) must also be on.

SW2 (2): Tri-level Alarm Enable/Disable

SW2, position 2 is used to enable or disable the “Tri-level” alarms on the “Equipment fail and Standby / Line
fail” Alarm pins (pin #6 & pin #3 of J3, respectively).

SW2 (2) Tri-level Alarm
OFF

Tri-level alarm function is disabled.

ON

Tri-level alarm function is enabled.

NOTE:

For proper operation of “Tri-level” alarm, SW2 (1) and SW2 (3) must also be on in conjunction with SW2 (2).

SW2 (3): Standby/Line Fail Alarm Pull-up Select

SW2, position 3 is used to enable or disable the 10k Ohm pull-up to AUX DC on the system’s transponder
“Standby / Line Fail” pin (pin #3 of J3).

SW2 (3): Standby/Line Fail Alarm Pull-up
OFF

Open collector output with no pull-up.

ON

Open collector output with 10k pull-up to AUX DC.

NOTE:

For “Tri-level” alarm see SW2 (2), SW2 (3) must also be ON.

SW2 (4): Output Fail Alarm Pull-up Select

SW2, position 4 is used to enable or disable the 10k Ohm pull-up to AUX DC on the system’s transponder
“Output Alarms” pin (Pin #10 of J3).

SW2 (4) Output Fail Alarm Pull-up
OFF

Open collector output with no pull-up.

ON

Open collector output with 10k pull-up to AUX DC.