REMOTE CONTROL
/ MONITOR

On/Off control via contact closure, 6-120 VDC or 12-240 VAC, and TTL or
CMOS switch, output voltage and current monitor, OVP limit set, summary fault status

PARAMETER

SPECIFICATION

FRONT PANEL AND REMOTE DIGITAL PROGRAMMING

Voltage

A-Panel: ±0.5% of full-scale + 1 Digit K-Panel: ±0.1% of full-scale

Current

A-Panel: ±0.5% of full-scale + 1 Digit K-Panel: ±0.4% of full-scale

Overvoltage Protection (OVP)

±1% of full-scale output

REMOTE DIGITAL READBACK

Voltage

±0.15% of full-scale

Current

±0.4% of full-scale

REMOTE ANALOG PROGRAMMING

Constant Voltage

±0.25% of full-scale output for 0-5V range (±0.5% 0-10V range)

Constant Current

±0.8% (40-800V output), ±1.0% (10-30V output) of full-scale output

Overvoltage Protection (OVP)

±1% of full-scale output

REMOTE ANALOG READBACK

Voltage

±1% (40-800V output), ±0.5% (10-30V output) of full-scale output

Current

±1% (40-800V output), ±0.5% (10-30V output) of full-scale output

RESISTIVE ANALOG PROGRAMMING

Constant Voltage (0-100%)

0-5 kΩ

Constant Current (0-100%)

0-5 kΩ

VOLTAGE ANALOG PROGRAMMING

Constant Voltage (0-100%)

0-5 VDC or 0-10 VDC

Constant Current (0-100%)

0-5 VDC or 0-10 VDC

REMOTE SENSING

Terminals are provided to sense output voltage at point of load. Maximum line drop 5% of rated voltage per
line for 40-100V models, line drop 1V of rated voltage per line for 10-20V models, 1.5V for 30V models, 2%
of rated voltage per line for models 160V and greater. (Greater line drop is allowed, but output regulation
specifications no longer apply).

REMOTE ANALOG CONTROL
Input to Output Isolation

The control signal return for Non-Isolated Analog programming is connected to the negative output termi-
nal. Under no condition should the negative terminal exceed 300V to earth ground. The maximum voltage
from control signal return of the Remote Isolated Analog programming (option) to the negative output
terminal is 600V.

PHYSICAL

3U MODELS (10V-30V)

3U Models (40V-800V)

6U MODELS (40V-600V)

WIDTH

19.00 in (48.3 cm)

19.00 in (48.3 cm)

19.00 in (48.3 cm)

DEPTH

28.09 in (71.4 cm)

26.4 in (67.1 cm)

27.06 in (63.8 cm)

HEIGHT

5.25 in (13.3 cm)

5.25 in (13.3 cm)

10.5 in (26.7 cm)

WEIGHT (Physical)

(4kW, 10V 15V) ≈<65 lbs (29 kg)
(5kW, 20V 30V) ≈<65 lbs (29 kg)
(8kW, 10V 15V) ≈<85 lbs (39 kg)
(10kW, 20V 30V) ≈<85 lbs (39 kg)
(12kW, 10V 15V) ≈<110 lbs (50 kg)
(15kW, 20V 30V) ≈<110 lbs (50 kg)

(5kW) ≈ 40 lbs (18 kg)
(10kW) ≈ 60 lbs (27 kg)
(15kW) ≈ 80 lbs (36 kg)

(20kW) ≈ 120 lbs (54 kg)
(25kW) ≈ 140 lbs (64 kg)
(30kW) ≈ 160 lbs (73 kg)

Important Notes:
1) Specifications are subject to change without notice
2) The SPS Series power supplies are intended for indoor use only.

Note: AMREL is the registered trademark of AMERICAN RELIANCE, INC and is being used by permission

Advertising