Instrument specifications – Atec AdaptivePowerSystems-1000 Series User Manual

Page 2

Advertising
background image

MODEL

1002

1003

1005

1010

1020

1030

1040

INPUT SPECIFICATIONS

Phase

1Ø/2W + ground

3Ø/3W + ground

Voltage

230V±15%

220, 240, 380, 415, 480V±10%

Frequency

47-63Hz

OUTPUT SPECIFICATIONS

Power rating

2kVA

3kVA

5kVA

10kVA

20kVA

30kVA

40kVA

Max Arms @

0-150 V

16.8 A

25.2 A

42 A

84 A

168 A

252 A

336 A

Max Arms @

0-300 V

8.4 A

12.6 A

21 A

42 A

84 A

126 A

168 A

Phase

1Ø/3W (L, N, G)

Voltage

Low Range

0-150V

HIgh Range

0-300V

Resolution

0.1V

Accuracy

±(1%+0.2V)

Frequency

Range

45-500Hz

Resolution

0.1Hz at 45-99.9Hz, 1Hz at 100-500Hz

Accuracy

±0.2%

Harmonic Distortion

≤1%(Resistance Load)

Crest Factor

≥3 to 1

Load Regulation

±0.5%

Protection

Over Current, Short Circuit, Over Temperature

Efficiency

≥85% (at full load)

Operating Temperature

32°-104°F, (0°-40°C), 80% Relative Humidity

Altitude

below 6500 feet

DISPLAYS AND CONTROLS

4 Digital LED meters

Frequency, Voltage, Current, Power or Power Factor (simultaneously)

PLC Remote Interface

M1, M2, M3, and Output On/Off

Memory

3 Programmable Memory Locations for Voltage, Frequency and Current

Calibration

Front Panel Calibration

Auto voltage adjust

Enable for improved voltage regulation within ±0.1V

MECHANICAL SPECIFICATIONS

2kVA

3kVA

5kVA

10kVA

20kVA

30kVA

40kVA

Dimensions (HxDxW) Inches

12x26x17

12x26x17

12x26x17

28x26x17

34x26x17

38x36x24

43x36x24

Weights (Kg/lbs)

60/132

65/143

80/175

200/440

315/695

465/1025

550/1210

©2003 ADAPTIVE POWER SYSTEMS, Irvine, CA, U.S.A. Subject to change without notice.