Vlf fault locator combination, Vlf-200cmf, Vt33(f) – Atec High-Voltage-VLF-28CMF User Manual

Page 6

Advertising
background image

6

HIGH VOLTAGE, INC.

31 County Route 7A • Copake, NY 12516 • (518) 329-3275 • Fax: (518) 329-3271 • www.hvinc.com

VLF-200CMF

The

VLF-200CMF provides a 200kVac peak output voltage, suitable for per-

forming VLF hipot tests on 138kV cable and as a voltage source for tan delta and

partial discharge testing on 230kV cable. The controls offer all the features of our

other VLF models along with VLF Cable Burning. Trailer mount optional.

Input:

230V Single phase, 80A peak, 50/60Hz

Output:

0 – 200 kVac peak, 100mA. Bushing output with no cable provided

Load:

.75 mF @ 0.1Hz, 1.5 mF @ 0.05Hz, 3.75 mF @ 0.02Hz

Duty:

Continuous

Metering:

Voltage: 0 – 200 kVac peak 3.5” analog display

Current: 0 – 200 mAac 3.5” analog display

Controls:

HV On/Off, Motorized Voltage Control, Zero Start Interlock,

External Interlock, Digital Dwell Timer, Capacitance Measuring

Circuit, Cable Burn Mode, Fixed 120% Overload,

Automatic Data Logger

Size/Weight: Controls: 24”w x 25.5”d x 71”h, 650lbs.

61cm h x 65cm w x 180cm h, 295kg

HV Tank: 59”w x 37”d x 87”h, 3700lbs

155cm w x 93cm d x 220cm h, 1678kg

VLF Fault Locator Combination

Input:

VT33: 120V, 60 Hz, 10A

VT33F: 230V, 50/60 Hz, 5A

VLF Hipot Output: 0 – 33 kVac peak @ 0.1 Hz

Load Capability: 1 mF or more than 1 mile (1.6 km) of 15 kV & 25 kV cable

Discharge Output: 0 – 13 kVdc @ 760 joules

Discharge Rate: Every 8 seconds

VLF Burner:

Arcs cable every few seconds using cable energy to burn.

TDR Interface:

Arc Reflection & Current Impulse

Size & Weight:

28”w x 26”d x 44”h, 245 lbs.

711mm w x 660mm d x 1118mm h, 111kg

Cable Outputs:

50’ (15m) shielded HV cable & ground

VT33(F)

The

VT33

is the worlds only combination VLF hipot and cable fault locator,

or thumper. It is the complete tool for AC testing and fault locating cables

rated up to 25kV. It offers a 33kVac peak VLF output, VLF Cable Burn

mode, and a 760 joule discharge output. It is fully TDR/radar ready.

Input:

230 volts, 50/60 Hz, 30A peak, 25A average

Output:

0-120 kVac peak, 0.1/0.05/0.02/0.01 Hz sinusoidal

Duty:

Continuous

Load Rating:

.55 mF @ 0.1 Hz, 1.1mF @ 0.05 Hz

2.75 mF @ 0.02 Hz, 5.5mF @ 0.01 Hz

Metering:

Voltmeter: 0-120 kVac peak

Charging Current Meter: 0 – 100 mA peak

Load capacitance meter: 0 – 6 microfarads

User programmable test duration timer

Cable Lengths: Shielded EPR output cable 100 ft. (30m)

Ground cable 100 ft. (30m)

Sizes & Weight: Controls: 17” w x 11” d x 9.5” h, 20 lbs.

432mm w x 280mm d x 241mm h, 9 kg

Regulator: 20” w x 14” d x 27” h, 160 lbs.

508mm w x 356mm d x 686mm h, 73 kg

HV Tank: 26” w x 20” d x 22” h, 390 lbs.

660mm w x 508mm d x 559mm h, 177 kg

Overall:

30” w x 60” d x 51” h, 853 lbs.

762mm w x 1524mm d x 1295mm h, 388 kg

VLF-12011CMF

The

VLF-12011CMF provides a 120kVac peak output voltage, suitable for VLF

hipot testing 69kV cable and as a voltage source for partial discharge and tan

delta testing of 115kV cable. In addition to the standard controls described, this

model also contains a Cable Burn mode. Cable reels provide 100’ (30m) of HV

and ground cable.

The Testing

Service &

Electrical

Contractor