Product specifications – Atec Sorensen-SG Series User Manual

Page 4

Advertising
background image

Common

Remote Sense

Load-line loss compensation for models <= 100 V
is 10% above full scale voltage total (5% per
load-line), and models > 100 V is 4% above full
scale voltage total (2% per load-line).

Parallel Operation

Up to 5 units may be paralleled for additional cur-
rent within the power supply single-unit specifica-
tions, with exception of the DC output current set
accuracy. Additional paralleled SG units will add
0.3% inaccuracy per unit. To parallel more than 5
units, contact factory.

Series Operation

Up to 2 units (see Output Float Voltage)

Input

Nominal Voltage
3 phase, 3 wire + ground

208/220 VAC (operating range 187 - 242 VAC)
380/400 VAC (operating range 342 - 440 VAC)
440/480 VAC (operating range 396 - 528 VAC)*
*Optional

Frequency

47 – 63Hz

Power Factor

>0.9 typical at 208/220 VAC input
>0.78 typical at 380/400 VAC input
>0.69 typical at 440/480 VAC input

Protection

½ cycle ride-though on all three phases, 3 cycle ride
through on single phase; missing phase shutdown

Output: Voltage and Current Ranges

3U

6U

Ripple &

Noise

Power

5

kW

10

kW

15

kW

20

kW

25

kW

30

kW

rms

(20 Hz-

300 kHz)

p-p

(20 Hz-

20 MHz)

Voltage

Current

40

125

250

375

500* 625* 750*

20 mV

75 mV

60

83

167

250

333

417

500

20 mV

75 mV

80

63

125

188

250

313

375

20 mV

100 mV

100

50

100

150

200

250

300

20 mV

100 mV

160

31

63

94

125

156

188

25 mV

150 mV

200

25

50

75

100

125

150

25 mV

175 mV

250

20

40

60

80

100

120

30 mV

200 mV

330

15

30

45

61

76

91

30 mV

200 mV

400

12

25

38

50

63

75

30 mV

300 mV

600

8

17

25

33

42

50

60 mV

350 mV

* By way of paralleling 5 kW, 10 kW & 15 kW supplies

Elgar Electronics Corp. • 9250 Brown Deer Road, San Diego, CA 92121. • 858.450.0085 • 858.458.0267 • [email protected] • www.Elgar.com

Product Specifications

Environmental

Operating Temperature

0 to 50º C

Storage Temperature

-25º C to 65º C

Humidity Range

Relative humidity up to 95% non-condensing, 0º C – 50º C

Altitude

Operating full power available up to 5,000 ft.
(~1,500 m), derate 10% of full power for every 1,000
feet higher; non-operating to 40,000 ft. (~12,000 m)

Cooling

Front and side air inlet, rear exhaust.
Units may be stacked without spacing.

Regulatory

Certified to UL/CSA 61010 and IEC/EN 61010-1, CE
Compliant, Semi-F47 Compliant

Physical

Dimensions

Width: 19.00” (48.3 cm), Depth 25.0” (63.5 cm)
Height:
5-15 kW units: 3U – 5.25” rack mount (13.34 cm)
20-30 kW units: 6U – 10.5” rack mount (26.67 cm)

Weight

3U < 80 lbs. (36 kg) 6U <160 lbs. (73 kg)

Shipping Weight

See web site for more product & shipping weights.

Output

Ripple & Noise
(Voltage Mode)

See Output: Voltage & Current Ranges Chart Above.
Ripple and noise specified at full load, nominal AC input

Ripple (Current Mode)

<+/- 0.04% of full scale rms current

DC Voltage Slew Rate

100 ms 5-95% of full scale typical
(Contact factory for model specific slew rates)

DC Current Slew Rate

45A / ms typical

Line Regulation

(±10% of nominal AC input, constant load)
Voltage Mode: +/- 0.01% of full scale
Current Mode: +/- 0.05% of full scale

Load Regulation

(no load to full load, nominal AC input)
Voltage Mode: +/- 0.02% of full scale
Current Mode: +/- 0.1% of full scale

Load Transient
Response

Recovers within 1ms to +/-0.75% of steadystate
output for a 50% to 100% or 100% to 50% load change

Efficiency

87% typical at nominal line and max load

Stability

±0.05% of set point after 8 hrs. warm-up at fixed line,
load and temperature

Temperature Coefficient

0.02%/ C of maximum output voltage rating for volt-
age set point
0.03%/ C of maximum output current rating for cur-
rent set point

Output Float Voltage

Negative terminal within +/- 150 V
of chassis potential.

Programming & Read-back Specifications

Programming

Read-Back / Monitoring

Accuracy

Resolution

Accuracy

Resolution

Front panel

Display

SGA: +/- (0.5%fs + 1 digit)

SGI, Voltage: +/- 0.1% of full scale

SGI, Current: +/- 0.4% of full scale

SGA: 3.5 digits

SGI: 4.0 digits

SGA: +/- (0.5%fs + 1 digit)

SGI, Voltage: +/- 0.1% of full scale

SGI, Current: +/- 0.4% of full scale

SGA: 3.5 digits

SGI: 4.0 digits

Knob control & Display read-back

Remote

Analog

Interface

Voltage: +/-0.25% of full scale for

0-5 V range, +/-0.5% of full scale

for 0-10 V range

Current: 0.8% of full scale

NA

+/-1.0% of full scale

(0 - 10V)

NA

25-pin D-sub connector (0~5 V or 0~10 V)

Remote

Digital

Interface

Voltage: +/- 0.1% of full scale,

Current: +/- 0.4% of full scale

+/-0.002% of

full scale

Voltage: +/- 0.15% of full scale,

Current: +/- 0.4% of full scale

+/-0.002% of

full scale

RS-232C (Standard on SGI), Optional IEEE-

488.2 and Optional LXI Compliant 10/100

base-T Ethernet (see Options)

OVP

+/- 1% of full scale

+/-0.002% of

full scale

Programming range: 5-110% Configured

from front panel, remote analog or via

optional digital inputs

User I/O

Disconnect & Polarity-reversal relay control ( Only available with Ethernet Option )

Digital 10-pin Molex type connector

See www.elgar.com/go/pinouts

Software

IVI & CVI drivers available under SUPPORT at: www.Elgar.com

EEC102706