BRAY Series 52 Valve Status Monitor

Operation and Maintenance Manual

18

Customer has an AS-i (Actuator Sensor Interface) controller with an AS-i approved 24VDC power sup-
ply. Once your customer has the configuration software (usually provided with the controller) they can
scan the bus and configure any AS-i device connected. Up to 62 devices can be connected to one con-
troller (V2.1 or 3), in applications requiring several valve status monitors, cost is greatly reduced when
only one single module can control 62 devices versus having to purchase a PLC input module for every
three to four S52s that you have.

Application Example #2 (AS-i S52)

1) Bray S52 is connected to the AS-i
BUS and is located at address 12.

2) By selecting the device at address
12, a configuration window allows
you to modify the device address,
check input state, and test the output.

3) Input 1 is shown in the ‘On’ State, Input 0
is ‘Off’, and the Output to the solenoid is not
energized.

AS-i bus

AS-i slave (1 of 62), Bray S52 P/Ns:
52-1005-12624-536 (kit) includes:
- 52-1005-71114-536 (S52)
- 52-1000-14821-533 (target)
52-1000-14805-533 (indicator)

AS-i Controller and
AS-i 24VDC Power Supply