Electrical troubleshooting – Dings Magnetic Group Stationary Electro Overhead Magnets User Manual

Page 11

Advertising
background image

Revised January 19, 2011

ELECTRICAL TROUBLESHOOTING

Before starting, first follow this preliminary checklist:

1.

Check all fuses and/or circuit breakers. For fuses, use a dual element time delay fuse

with a maximum of 175% of the full load current to protect the input side of the rectifier.

If 175% of full load amps does not correspond to a standard fuse size, select the next

larger standard fuse size (but do not exceed 225%). For circuit breakers, use a n

inverse time circuit breaker with a maximum of 250% of full load current. If 250% does

not correspond to a standard circuit breaker size, select the next larger standard circuit

breaker size (but do not exceed 400% for 100 amps or less).

2.

Check all wiring for loose or broken connections.

3.

Visually inspect all internal rectifier components.

4.

If equipped with a starter, check all overloads (bi-metallic components) to see if any

have tripped. Wait several minutes before resetting.

5.

If equipped with a starter, check to see if correct heaters for selected voltage are

installed and that load does not exceed nameplate rating.

6.

Do not ground the DC circuit supplying the magnet or damage will occur.

WARNING

The following procedures should be performed by a qualified electrician. Extreme caution

should be used as live electrical equipment will be tested. Before starting the testing

procedure, turn off and lock-out any surrounding equipment that may pose a danger during

testing. If the magnet is of the self-cleaning type, turn off and lock-out the power to the self-

cleaning belt motor. The following instructions are for standard 230 VAC or 460 VAC, 3 phase,

60 Hz rectifiers. For special input voltages, consult factory.


STEP 1

Disconnect the DC cable leads to the magnet AT THE RECTIFIER TERMINAL BLOCK inside

the rectifier cabinet. Turn on the power to the rectifier. Measure the AC input voltage to the

rectifier at the terminal block.

1st Reading Phase 1 to Phase 2 Volts:

2nd Reading Phase 2 to Phase 3 Volts:

3rd Reading Phase 3 to Phase 1 Volts:

If all three voltage readings are within the following tolerances, the power supplying the rectifier

is OK. Go to Step 2.

230 VAC + 5% for 230 VAC input rated rectifiers.

460 VAC + 5% for 460 VAC input rated rectifiers.

If one or more of the voltage readings are out of tolerance, the power supplied to the rectifier is

incorrect and must be corrected.

9

Advertising