Rectifier input over-current protection – Dings Magnetic Group Stationary Electro Overhead Magnets User Manual

Page 8

Advertising
background image

Revised January 19, 2011

RECTIFIER INPUT OVER-CURRENT PROTECTION

All rectifiers contain a transformer. A transformer has all the same component parts as a

motor, and like a motor, exhibit a current inrush when energized. This inrush current is

dependent upon where in the sine wave the transformer was last turned off in relation to where

in the sine wave the transformer is when you energize it. Although transformer current inrush

could run up to 30 to 35 times full load current under a no load condition, it typically will be the

same as a motor at about 6 to 8 times the full load current. For this reason it is important to

use a dual element time delay type fuse, the same type of fuse you would use with a motor. If

using circuit breakers, select a breaker with a time delay, again the same type you would use

with a motor. If the time delay is not sufficient, you may experience “nuisance tripping”, a

condition where the circuit breaker trips when energizing the transformer but when you try it

again, it works fine.


Fuses

Use a dual element time delay fuse or a circuit breaker with a time delay having a rating of 175

percent of the full load current to protect the input side of the rectifier. If 175% of full load

amps does not correspond to a standard fuse size, select the next larger standard fuse size

(but not exceeding 225%).


Circuit Breakers

Use an inverse time circuit breaker with a maximum rating of 250% of the full load current. If

250% of full load amps does not correspond to a standard circuit breaker size, select the next

larger size (but not exceeding 400%).


Caution:

Always follow the latest edition of the National Electric Code and any other applicable codes

for over-current protection of 600-volt class transformers to determine the proper over-current

protection for rectifiers. One special consideration not listed in the above codes is to be careful

of the type of fuse or circuit breaker used to protect the input side of the transformer.


EXAMPLE:

Model 33 Electro Magnet

5 kW, NEMA 12 Rectifier

AC input: 460 VAC/3phase/60 Hz, 6.7 amps

Time Delay Fuses

6.7 amps x 175% = 11.73 amps 11.73 is a non-standard fuse size. The next standard fuse

size is 12 amps. 12 amps is 179% of the full load amps, but is under the 225% maximum limit.

USE A 12 AMP TIME DELAY FUSE.

Circuit Breakers

6.7 amps x 250% = 16.75 amps. 16.75 is a non-standard circuit breaker size. The next

standard circuit breaker size is 20 amps. 20 amps is 299% of full load amps, but under the

400% maximum limit. USE A 20 AMP INVERSE TIME CIRCUIT BREAKER.

6

Advertising