L1 l2 l3 – Schreiber Chillers 100ACsf User Manual
Page 7
Advertising

Models:
Voltage:
Options:
220-460
100AC
Schreiber Engineering Corp.
12111 Park St. Cerritos, CA 90701
(562)-926-3855
(562)-926-0969 Fax
Phase: 3
Type: Air Cooled
Notes:
All motors have internal overload protection unless otherwise shown
On all connections: L1 - Blue L2 - Black L3- Red
Marks:
1W
1C
T1
T2
T3
T1
T2
T3
T1
T2
T3
1W
1C
Water Pump Starter
Coil
Compressor 1 Starter Coil
Low Pressure
Switch
High
Pressure
Switch
Compresor
Manual Switch
Pump
Manual
Switch
Thermostat
L1
L2
L3
Step Down Transformer
24v secondary
40va rating
Normally Closed
Trip Setpoint is
15 Psig
Normally Closed
Trip Setpoint is
425 Psig
In-rush Current .400 Amps
In-rush Current .400 Amps
6
5
4
3
7
8
1
2
R
R
2
P
-U
A
C
2
4
V
5
0
/
6
0
H
z
id
e
c
Tank fill solenoid
Advertising