1 humidity and ambient temperature, 2 maximum floor loading, 3 water composition – A.O. Smith BFC - 28 User Manual

Page 18: 4 working clearances, Humidity and ambient temperature, Maximum floor loading, Water composition, Working clearances

Advertising
background image

Installation

18

Instruction Manual BFC

3

is

3.3.1

Humidity and ambient temperature

The boiler room must be frost-free, or be protected against frost.

Table 3.1

shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the appliance to be guaranteed.

3.3.2

Maximum floor loading

In connection with the appliance’s weight, take account of the maximum floor
loading, see

Table 3.2

.

3.3.3

Water composition

The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.

Table 3.3

shows these requirements.

n

Remark

If the water specifications deviate from those stated in

Table 3.3

, then the

tank protection cannot be guaranteed.
See also chapter

’13 Warranty (Certificate)’

.

3.3.4

Working clearances

For access to the appliance it is recommended that the following clearances
are observed (see

Figure 3.2

):

AA: around the appliance’s control column and cleaning openings: 100 cm.

BB: around the appliance itself: 50 cm.

Above the appliance (room to replace the anodes):
-

100 cm if using fixed anodes, or

-

50 cm if using flexible anodes.

Table 3.1 Humidity and ambient temperature specifications

Humidity and

ambient

temperature

Humidity

max. 93% RH at +25°C

Ambient temperature

Functional: 0

≤ t ≤ 60°C

Table 3.2 Weight specifications related to maximum floor loading

Weight of the appliance filled with water

BFC 28

392 kg

BFC 30, BFC 50, BFC 60

593 kg

Table 3.3 Water specifications

Water composition

Hardness

(alkaline earth ions)

> 1.00 mmol/l:

German hardness >5.6° dH

French hardness > 10.0° fH

British hardness > 7.0° eH

Conductivity

> 125

µS/cm

Acidity (pH value)

7.0 < pH value < 9.5

Advertising