Caution – AAON V3-E User Manual

Page 23

Advertising
background image

23

inches away from all components and wiring
to prevent damage due to drilling or cutting.
2. Drill a pilot hole all the way through the
foam panel.
3. Using a hole saw cut the hole through the
metal on both sides of the foam part.
4. With a knife cut the foam out of the hole.
5. After the conduit is installed in the hole
caulk the entire perimeter of the hole on
both sides with an industrial grade silicone
sealant or a duct seal compound.


If a larger cut-out is needed for additional
duct connections not provided by the
factory, or for any other reason, it is very
important that the foam be completely
sealed.

Insulation

covers

should

be

fabricated from sheet metal to cover the
foam at the cut. The edges and corners that
are not covered should then be sealed using
silicone caulking or a duct seal compound.

If a reciprocating saw is used to make the
cut-out take care that the metal skins of the
foam part do not separate from the foam,
this would result in reduced structural
integrity of the part.

Size supply conductors based on the unit
Minimum Current Ampacity (MCA) rating.
Supply conductors must be rated a minimum
of 75°C.

Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the

current

National

Electric

Code,

ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.

Note: Units are factory wired for 208V,
230V, 460V or 575V. In some units, the
208V and 230V options may also be
provided

in

single

or

three

phase

configurations.

The

transformer

configuration must be checked by a
qualified technician prior to startup.

Wire power leads to the unit’s terminal
block or main disconnect. All wiring beyond
this point has been completed by AAON and
cannot be modified without effecting the
unit’s agency/safety certification.


Supply voltage must be within the min/max
range shown on the unit nameplate.
Available short circuit current should not
exceed the short circuit current rating
(SCCR) shown on the unit nameplate.








Three phase voltage imbalance will cause
motor overheating and premature failure.
The maximum allowable imbalance is 2.0%.

Voltage imbalance is defined as 100 times
the maximum deviation from the average
voltage divided by the average voltage.

Example:
(221V+230V+227V)/3

=

226V,

then

100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.

Check voltage imbalance at the unit
disconnect switch and at the compressor


Installing Contractor is responsible
for proper sealing of the electrical
and gas entries into the unit. Failure
to seal the entries may result in
damage to the unit and property.



Three phase voltage imbalance will
cause

motor

overheating

and

premature failure.

CAUTION

CAUTION

Advertising
This manual is related to the following products: