Variable Capacity Compressor
Controller

Units

with

variable

capacity

scroll

compressors may include the following
compressor controller. The following is an
explanation

of

the

terminals

and

troubleshooting alert flash codes of the
controller. For more information on the
compressor controller, see Emerson Climate
Bulletin AE8-1328.

Figure 35 - Variable Capacity Compressor

Controller


Low Voltage Terminals
24COM

Module Common

24VAC

Module Power

C1 & C2

Demand Input

P1

Pressure Common

P2

Pressure Input

P3

Pressure Power 5VDC

P4

Pressure Shield

P5 & P6

Pressure Output

T1 & T2

Discharge Temperature Sensor

High Voltage Terminals
A1 & A2

Alarm Relay Out

M1 & M2

Contractor

L1

Control Voltage N

L2

Control Voltage L

U1 & U2

Digital Unloader Solenoid

V1 & V2

Vapor Injection Solenoid









The compressor controller modulates the
compressor unloader solenoid in an on/off
pattern according to the capacity demand
signal of the system. The following table
shows the linear relationship between the
demand signal and compressor capacity
modulation. The compressor controller
protects the compressor against high
discharge temperature. Refer to Appendix B
for the relationship between thermistor
temperature readings and resistance values.









Table 17 - Demand Signal vs. Compressor Capacity Modulation

Demand

Signal (VDC)

Loaded %

Unloaded %

Time Loaded

Time

Unloaded

% Compressor

Capacity

1.00

Off

Off

Off

Off

0%

1.44

10%

90%

1.5 sec

13.5 sec

10%

3.00

50%

50%

7.5 sec

7.5 sec

50%

4.20

80%

20%

12 sec

3 sec

80%

5.00

100%

0%

15 sec

0 sec

100%

To avoid damaging the Compressor
Controller do not connect wires to
terminals C3, C4, T3, T4, T5, or T6.

WARNING