Table 2 - Electric Heat Maximum

Overcurrent Protection

230V 208V Line

1

Line

2

Line

3

kW kW MOP MOP MOP

5 3.75 30

10 7.50 60

15 11.25 60 30

20 15.00 60 60

25 18.75 60 60 30


Heat Pump
For heat pump equipped split system
configurations, the heat pump is the primary
heat source during a call for heat. During
operation at low ambient temperatures
where the heat pump alone cannot satisfy
the space temperature set point, electric
resistance heat elements are activated.

Below about 17°F, only the electric heat is
operable; the heat pump is not active.


ECM Driven Fan
The Electrically Commutated Motor (ECM)
has selectable fan speeds as determined by
the configuration of four pins as shown in
FIGURE 2.

Figure 2 - Example Configuration of ECM

Fan Taps


Adjust the taps as desired for cooling,
dehumidification, and heating according to
the following instructions.

Cooling:
Units are preprogrammed from the factory
for a rated airflow rate of 400 cfm per ton as
shown in Table 3.

Table 3 - Factory Preset Air Flow

Model Preset

cfm

F1-060 2000
F1-048 1600
F1-036 1200
F1-024 800

* Maximum total static is 2.25” w.g.

The high speed for cooling may be selected
by setting the COOL and ADJUST fan
speed taps (shown in Figure 2). The setting
combinations are shown in Table 4.

Note: On the ADJUST tap, both of the ‘1’
selections have the same effect on motor
speed.

Table 4 - Cooling Fan Speed Tap Settings

F1-060/ F1-036/

COOL

Tap

ADJUST

Tap

F1-048 F1-024

(cfm) (cfm)

2000 1200

A

1

2000 1200

D

1

1840 1150

B

+

1700 1020

A

-

1700 1020

D

-

1600 1000

B

1

1380 920

C

+

1360 850

B

-

1200 800

C

1

1020 680

C

-


A signal from the thermostat, showing a
need for dehumidification, will cause the
unit to slow the fan speed in order to allow
the air moving across the coil to get colder
thereby better dehumidifying the air. Fist
stage dehumidification has a low fan speed
of 67% of the selected max speed. Second
stage dehumidification has a fan speed of
45% of the selected max speed. NOTE: The
Modulating Hot Gas Reheat option must be
selected to have a second stage of
dehumidification.

A

----

A

- -

1

- -

A

----

B

- -

B

- -

+

- -

B

- -

C

- -

C

- -

-

----

C

- -

D

- -

D

----

1

- -

D

- -

HEAT

COOL

ADJUST

DELAY