INSTALLATION continued

AAON Rooftop units are designed for fast, easy installa-
tion. The curb is mounted first and must be located so
that duct connections will be clear of structural mem-
bers of the building.

SETTING THE CURB
When using the factory curb, make openings in roof
decking large enough to allow for duct penetrations and
workspace only. Do not make openings larger than
necessary. Set the curb to coincide with the openings.
Make sure the curb is level.

SETTING THE UNIT

If cables or chains are used to hoist the unit they must be
the same length and care should be taken to prevent
damage to the cabinet / coils or condenser fans.
It is recommended lifting the unit with the outside air
hood in the downward shipping position, however the
unit may be lifted with the outside air hood in the open
position.

Before lifting unit, be sure that all shipping material has
been removed from unit. Secure hooks and cables at all
lifting points / lugs provided on the unit.

Hoist unit to a point directly above the curb and duct
openings. Lower unit while guiding the unit to align with
utility opening and duct openings. Be sure that the
gasket material has been applied to curb. Continue low-
ering the unit until the unit skirt fits around the curb.
Make sure the unit is properly seated on the curb and is
level.

LIFTING DETAIL

TYPICAL FOR

2 - 25 TON UNITS

99" minimum

length

LIFTING DETAIL

TYPICAL FOR

26 - 60 TON UNITS

180" minimum

length

Where the supply or warm air duct passes

through a combustible roof, a clearance

of one inch must be maintained between

the outside edges of the duct and

combustible material in accordance

with National Fire Protection Association

Standard No. 90A. Provide flashings or

enclosure between structure and roof

and all joints must be sealed with mastic

roofing to ensure a watertight seal.

All roofing work should be performed by

competent roofing contractors to avoid

any possible leakage.

!

CAUTION

Improper installation, adjustment,

alteration, service or maintenance can

cause property damage, personal injury

or loss of life. Installation and service must

be performed by a qualified installer,

service agency or the gas supplier.

Install the gas fired unit to assure the flow

of combustion and ventilating air is not

obstructed from reaching the heater and

that the flue outlet is located at least

120 inches away from any opening

through which combustion products

could enter the building.

!

WARNING

The unit shall be installed so that the rectangular flue (if
applicable) is located at least 120" away from any open-
ing through which combustion products could enter the
building. The unit shall also be installed so that the flow
of combustion and ventilating air is not obstructed from
reaching the furnace. Do not position flue opening to
discharge into a fresh air intake of any other piece of
equipment.