8




























































































PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used

with

R-410A

and

other

refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.

CAUTION


UNIT HANDLING


To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.

WARNING


Door

compartments

containing

hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.

CAUTION


Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service

technician.

Scroll

compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should

be

checked

for

proper

operation. Alterations should only be
made at the unit power connection

CAUTION


Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.

WARNING


To prevent damage to the unit, do not
use acidic chemical coil cleaners.
Use alkaline chemical coil cleaners
with a pH value of 5-9, after mixing,
without first using an aluminum
corrosion inhibitor in the cleaning
solution.

CAUTION


Some

chemical

coil

cleaning

compounds are caustic or toxic. Use
these substances only in accordance
with

the

manufacturer

’s

usage

instructions.

Failure

to

follow

instructions may result in equipment
damage, injury or death.

WARNING


Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.

CAUTION

Advertising