Specifications

1. Overview

ADT-APS-6R Instruction PN 50935:B 7/21/00

7

Specifications

The ADT-APS-6R is compatible with the Unimode II, Unimode 300/400,
Unimode 4-16 and Unimode 2020 control panels. Specifications for the
ADT-APS-6R are:

Table 2 ADT-APS-6R Specifications

Electrical Specifications

AC Primary Input Power
Wire Size: #14 AWG with
600 VAC insulation

120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A

24 VDC Secondary Input Power
(lead-acid batteries only)

25 mA DC standby current
16 mA DC standby current (with AC fail delay
operating)

Note: Batteries are charged by the system power supply.

24 VDC output power
Circuit 1
Circuit 2
Circuit 3

Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+10, –15%)
3 A @24 VDC power-limited (+10, –15%)
6 A @24 VDC non power-limited (+10, –15%)

Fuses
F1 (AC supervision)
F2 (battery supervision)

250 VAC, 4A, 3 AG, slow blow
32 VAC, 10 A, 3 AG, slow blow

Trouble supervision bus
J3 output
J4 input

Note: J3 and J4 can be
interchanged.

Form A contact (open collector)
Form A contact (open collector)

Loss of AC Indication

Immediate indication (default)
8 or 16 hour delay

Mechanical Specifications

Size of ADT-APS-6R in enclosure

6.09 in. x 4.23 in. x 2.92 in.

Cabinets for mounting

ADT-CAB-3 Series, using CHS-4 and CHS-4L
chassis, for Unimode 400, unimode II and
Unimode 2020 control panels.
ADT-CAB-400AA for Unimode 300/400
control panel; accepts one APS-6R.
Unimode 4-16 can accept one ADT-APS-6R.

Note: An optional module (such as an ICM-4) without an expansion card can
mount above an ADT-APS-6R in a CHS-4, a Unimode 4-16, and a
ADT-CAB-400AA.