Dynasonics Fusion Water Flow Meter User Manual

Page 23

Advertising
background image

23

2. Press the

►

key to display FL C-OFF on bottom display. Press

the ENTER key.

3. Press the

►

key to move one digit right and the

▲

key to

increment a flashing digit. Values are entered in flow rate
units.

4. Press the ENTER key.
5. Press the MENU key to exit.

OUTPUT -- Output Type

NONE - 4-20mA and Rate Pulse Outputs disabled

4-20MA - 4-20mA Analog Output

RATE - Rate Pulse Output (0-1,000 Hz)

Utilized to select either the 4-20mA or 1,000 Hz rate pulse
output.
1. To select either the mA or pulse output, press the MENU key.
2. Press the

►

key to display output on bottom display. Press

ENTER key.

3. Press the

►

key to select 4-20mA, pulse or none.

4. Press the ENTER key.
5. Press the MENU key to exit.


4

‐20TEST -- 4-20 mA Output Test

Allows a fixed current to be output from the 4-20 mA output. By

incrementing this value, the 4-20 mA output will transmit the
indicated current value.
The 4-20TEST prompt only appears if the output is
configured for 4-20mA output. The output will be spanned

between 0 flow and the value entered for Full Flow Rate.

Select the 4‐20TEST feature. Use the

▲

and

►

keys to increment/

decrement mA output current. Verify that at mid-scale, 12 mA,

that the receiving unit is showing 50% of full flow.

IMPORTANT: The RATE PULSE and 4-20 mA outputs cannot
be operated simultaneously. Select the desired output type

from the OUTPUT menu.