The flow rate is normalized to return 0 for min flow and 65535
for the maximum flow as specified in the system configuration for

Full Flow rate. (See page 23.)
Command: <addr><04><00><00><00><01><crc-16>

Reply:

<addr><04><02><data HI><data LO><crc-16>

The totalizer returns the displayed value in four 8 bit words.
Command: <addr><04><00><02><00><02><crc-16>

Reply:

<addr><04><04><MSW HI><MSW LO><LSW

HI><MSW LO><crc-16>

Opcode 05 – Force Single Coil
This opcode sets the state of a single coil (digital output).
The following Coil Registers are defined:

The transition of coil 9 from 0 to 1 will initiate function. This bit is
auto reset to 0, so there is no need to set it to 0 after a totalizer

reset command.
Command: <addr><05><00><08><FF><00><crc-16>
Reply:

<addr><05><00><08><FF><00><crc-16>

Coil #

Description

1..8 Spare

9 Reset

Totalizer

10.16 Spare