Addendum — Relay Alarm Module

Description: Installation and Operation Manual Addendum

Series D901/D90M Alarm Relay Option


Origin Date: 7-20-98

Revision: none

Revision date: none

Page 1 of 2

General

This addendum supplies information not covered in the standard Installation and
Operation Manual
supplied with the Series D901/D90M Ultrasonic Flowmeter Product.
The Series D901/D90M product enclosed in this carton was purchased with an
external relay alarm module. The module is enclosed and will need to be mounted
seperately from the D901/D90M enclosure.

Supplemental Specifications - Alarm Module

Loop Load equivalent 200

Ohms

Alarm Trip Point

Activated by setting trip point proportional to full scale FPS

(example:

to

trip

alarm at 2 FPS when FULL SCALE on

the D901 is set to 10 FPS. Set alarm to 2/10 = 20%.)

Contact Rating

SPDT, 3 AMPS @ 28Vdc or 117 VAC resistive.

Dead Band

DIP switch selectable, see chart below

Connections

Termination Inside the D901/D90M

Terminations at the Alarm Relay