Part 3 - keypad configuration – Dynasonics TFXM Series Ultrasonic Multi-Channel Flow Meter User Manual

Page 63

Advertising
background image


Rev. 8/02

-3. 25-

TFXM

SIG STR - Signal Strength

The measurement of Signal Strength assists service personnel
with troubleshooting the TFXM system. In general, expect the
signal strength readings to be greater than 5% on a full pipe
with the transducers properly mounted. Signal strength read-
ings that are less than 5% may indicate a need to chose an al-
ternative mounting method for the transducers or that an im-
proper pipe size has been entered.

Signal Strength readings in excess of 95% may indicate that a
mounting method with a longer path length may be required.
For example, if mounted on a 3 inch PVC pipe in V-mode
causes the measured Signal Strength value to exceed 95%,
change the mounting method to W-mode for greater stability in
readings.

PART 3 - KEYPAD CONFIGURATION

Deg. C

Deg. F

Vs (m/s)

Vs (f/s)

0

32

1402

4600

10

50

1447

4747

20

68

1482

4862

30

86

1509

4951

40

104

1529

5016

50

122

1543

5062

60

140

1551

5089

70

158

1555

5102

80

176

1554

5098

90

194

1550

5085

100

212

1543

5062

110

230

1532

5026

120

248

1519

4984

130

266

1503

4931

140

284

1485

4872

150

302

1466

4810

160

320

1440

4724

170

338

1412

4633

180

356

1390

4560

190

374

1360

4462

200

392

1333

4373

220

428

1268

4160

240

464

1192

3911

260

500

1110

3642

TABLE 3.1
Sound Speed in
Liquid Water
Vs.
Temperature

Signal Strength