Part 3 - keypad configuration – Dynasonics TFXM Series Ultrasonic Multi-Channel Flow Meter User Manual
Page 63

Rev. 8/02
-3. 25-
TFXM
SIG STR - Signal Strength
The measurement of Signal Strength assists service personnel
with troubleshooting the TFXM system. In general, expect the
signal strength readings to be greater than 5% on a full pipe
with the transducers properly mounted. Signal strength read-
ings that are less than 5% may indicate a need to chose an al-
ternative mounting method for the transducers or that an im-
proper pipe size has been entered.
Signal Strength readings in excess of 95% may indicate that a
mounting method with a longer path length may be required.
For example, if mounted on a 3 inch PVC pipe in V-mode
causes the measured Signal Strength value to exceed 95%,
change the mounting method to W-mode for greater stability in
readings.
PART 3 - KEYPAD CONFIGURATION
Deg. C
Deg. F
Vs (m/s)
Vs (f/s)
0
32
1402
4600
10
50
1447
4747
20
68
1482
4862
30
86
1509
4951
40
104
1529
5016
50
122
1543
5062
60
140
1551
5089
70
158
1555
5102
80
176
1554
5098
90
194
1550
5085
100
212
1543
5062
110
230
1532
5026
120
248
1519
4984
130
266
1503
4931
140
284
1485
4872
150
302
1466
4810
160
320
1440
4724
170
338
1412
4633
180
356
1390
4560
190
374
1360
4462
200
392
1333
4373
220
428
1268
4160
240
464
1192
3911
260
500
1110
3642
TABLE 3.1
Sound Speed in
Liquid Water
Vs.
Temperature
Signal Strength