Changing the settings, Setting the set point temperatures, 3 changing the settings – DE DIETRICH MIT iSystem User Manual

Page 17

Advertising
background image

User level - Menu #MEASURES
Parameter

Description

Unit ROE-II ROE-H ROE+ ROE+TH ROI+

HOT GAS TEMP.

Refrigerant temperature at the compressor outlet

°C

x

HOT GAS TEMP.

Compressor outlet temperature

°C

x

NB IMPULS.COMP

Number of heat pump start-ups

x

x

x

x

NB IMPULS.COMP.1

Number of start-ups on compressor 1

x

RUNTIME HP

Number of hours' operation of the heat pump

compressor

h

x

x

x

x

x

NB IMPULS.COMP.2

Number of start-ups on compressor 2

x

RUNTIME.COMP.2

Number of hours' operation of compressor 2

h

x

IN 0-10V

(1)

Voltage at input 0-10 V

V

x

x

x

x

x

SEQUENCE

Control system sequence

x

x

x

x

x

CTRL

Software control number (SCU)

x

x

x

x

x

(1) The parameter is only displayed for the options, circuits or sensors actually connected.

4.3

Changing the settings

4.3.1.

Setting the set point temperatures

To set the various heating, DHW and swimming pool temperatures,

proceed as follows:
1. Press the C key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.

4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.

To cancel, press key h.

Menu C
Parameter

Adjustment range Description

Factory setting

DAY TEMP. A

5 to 30 °C

Desired room temperature in comfort periods on circuit A

20 °C

NIGHT TEMP. A

5 to 30 °C

Desired room temperature in reduced periods on circuit A

16 °C

ROOMTEM.COOL A

(1)

(2)

22 to 30 °C

Desired room temperature set point in cooling mode

25 °C

DAY TEMP. B

(2)

5 to 30 °C

Desired room temperature in comfort periods on circuit B

20 °C

NIGHT TEMP. B

(2)

5 to 30 °C

Desired room temperature in reduced periods on circuit B

16 °C

ROOMTEM.COOL B

(2)

(1)

22 to 30 °C

Desired room temperature set point in cooling mode

25 °C

DAY TEMP. C

(2)

5 to 30 °C

Desired room temperature in comfort periods on circuit C

20 °C

NIGHT TEMP. C

(2)

5 to 30 °C

Desired room temperature in reduced periods on circuit C

16 °C

ROOMTEM.COOL C

(2)

(1)

22 to 30 °C

Desired room temperature set point in cooling mode

25 °C

WATER TEMP.

(2)

10 to 65 °C

Desired domestic hot water temperature in the DHW circuit 55 °C

(1) The parameter is only displayed if the corresponding circuit can handle cooling.

(2) The parameter is only displayed for the options, circuits or sensors actually connected.

MODE

C002266-A

MIT iSystem

4. Operating the appliance

24/05/2012 - 300028952-001-01

16