Setting the dhw calorifier outlet temperature, Programming and setting the electrical back, 3 setting the dhw calorifier outlet temperature – DE DIETRICH BSL 200...400 - BESL 200...400 User Manual

Page 16

Advertising
background image

1. Set the 3-position switch to 0.
2. Go forward to the last display channel (HRE) with the ( key.
3. Press the ( key for 5 seconds.

A setting parameter is displayed, with the symbol T.

4. Select parameter SX using keys ) and (.
5. Briefly press the B key.

The symbol T flashes, the parameter can be set.

6. Modify the parameter using the ( and ) keys.

For example 45(°C).

7. Press B to confirm the setting.

n Return from prolonged absence

On return from a prolonged absence:

4

Adjust the set point of the solar calorifier SX to its installation value.

4

Re-authorise the back-ups.

4

Set the 3-position switch to winter or summer, according to the

season.

4.3

Setting the DHW calorifier outlet temperature

4.3.1.

Programming and setting the electrical
back-up

The temperature of the volume of water heated by the electrical

resistor is set by the installer on commissioning of the installation

according to the size of the home.

Using the solar control system, it is possible to adjust the volume of

water heated to 40 °C by the resistor in two ways:

4

Force the continuous heating of the resistor for significant

unforeseen needs.
¼See chapter: "Force back-up", page 14.

4

Select winter mode w (2 hours maximum according to the volume

of the domestic hot water required at 40 °C) to compensate for the

lack of sun in winter. If necessary, the period scheduled outside of

the off-peak hours is set between 16:00 and 18:00, i.e at the end

of the day when the solar contribution is reduced and just before

the drawing off period.
¼See chapter: "Modifying the back-up authorisations", page

14.