mainTenance,

8.

TrOubleshOOTing

safety instructions

8.1.

Danger!

Risk of injury from high pressure in the equipment!

Before loosening the pipes and valves, turn off the

pressure and vent the pipes.

Risk of injury due to electrical shock!

Before reaching into the device or the equipment,

switch

off the power supply and secure to prevent reactivation!
Observe applicable accident prevention and safety

regulations for electrical equipment!

Warning!

Risk of injury from improper maintenance!

Maintenance may be carried out by authorized techni-

cians only and with the appropriate tools!

Risk of injury from unintentional activation of the
system and an uncontrolled restart!

Secure system from unintentional activation.

Following maintenance, ensure a controlled restart.

english

21

installation of pilot valve

8.2.

Warning!

Escaping medium!
When a sticking screw is loosened, medium may escape.

Do not tighten sticking screws any further.


Electric shock!
If the protective conductor is not connected, there is a
risk of electric shock!

Check protective conductor contact after installing the

coil

note!

If the tightening torque is too great, the device may
be damaged!

Observe the maximum tightening torque of the screws!


Device will be damaged if the wrong tools are used!

Always use a right tools to tighten screws. If other

tools are used (e.g. pliers), the device may be

damaged.

english

22

0.3 ± 0.05 Nm

0.2 ± 0.05 Nm

Installation of pilot valve

Fig. 4:

Attach pilot valve to Armature:

Tighten the screws with 0.2 ± 0.05 Nm.

Protective conductor function

Fig. 5:

english

23

Check functionality of the protective conductor

Resistance

Test voltage

Test current

max. 0,1 Ω

12 V

1 A

malfunctions

8.3.

If malfunctions occur, check whether:

the device has been installed according to the

instructions,
the electrical and fluid connections are correct,

the device is not damaged,

all screws have been tightened,

the voltage and pressure have been switched on,

the pipelines are clean.

Valve does not switch
Possible cause:

Short-circuit or coil interrupted,

Internal space of the valve is dirty,

Medium pressure outside the permitted pressure range.