Technical Data
6.
TECHNICAL DATA
6.1.
Operating Conditions
WARNING!
The Type 8605 is not designed for use outdoors!
• Do not use the Type 8605 outdoors and avoid heat sources which may result in the permitted temperature
range to be exceeded.
Power supply
12...24V DC ± 10%
Residual ripple 5 %
Power consumption
ca. 1 W
Output current (on the valve)
max. 2 A
Operating temperature
-10 ... 60º C / 14 ...140ºF
Interference resistance
to EN50082-2
Emission
to EN50081-2
Current range, depending
on the version for valves
40 ... 220 mA,
200 ... 1000 mA,
500 ... 2000 mA
Standard signal input
Voltage (0 ... 5, 0 ... 10 V)
input impedance > 20 kW
Current (0 ...20, 4 ... 20 mA)
input impedance <200 W
Housing: DIN rail version
Degree of protection
IP40 (DIN EN 60529)
Materials
Polyamide / PBT
Dimensions
LxBxH: 97x27x57 mm
Housing: Cable plug version
Degree of protection
IP65 (DIN EN 60529)
Materials
Polyamide / PC
Dimensions
LxBxH: 70x32x42.5 mm