Pneumaticinstallation

8

pneumaTic insTallaTiOn

Danger!

risk of injury from high pressure in the equipment/device.

▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.

Warning!

risk of injury from improper installation.

▶ Installation may be carried out by authorized technicians only and with the appropriate tools.

risk of injury from unintentional activation of the system and an uncontrolled restart.

▶ Secure system from unintentional activation.

▶ Following installation, ensure a controlled restart.

Procedure:

Connect the control medium to the pilot air port (1)
(3 – 7 bar; instrument air, free of oil, water and dust).

Attach the exhaust airline or a silencer to the exhaust air port (3) (see “Figure 17”).

Important information for the problem-free functioning of the device:

▶ The installation must not cause back pressure to build up.

▶ Select a hose for the connection with an adequate cross-section.

▶ The exhaust air line must be designed in such a way that no water or other liquid can get into the device

through the exhaust air port.

Exhaust air port
label: 3

Pilot air port
label: 1

Figure 17:

Pneumatic connection

Caution:

(Exhaust air concept):

In compliance with degree of protection IP67, an exhaust air line must be installed in the dry area.
Keep the adjacent supply pressure always at least 0.5 – 1 bar above the pressure which is required to
move the actuator to its end position.

english

Type 8691