Installation

note!

too high torque when screwing in the fastening screw does
not ensure degree of protection ip65 / ip67.

▶ The fastening screws may be tightened to a maximum torque of

0.5 Nm only.

→

Attach the Pneumatic Control Unit to the actuator using the two
side fastening screws. In doing so, tighten the fastening screws
hand-tight only (maximum torque: 0.5 Nm).

3. installation of the pneumatic connection on the actuator

Pilot air outlet 2

1

Lower pilot air port

Upper pilot air port

Pilot air outlet 2

2

Fig. 12: Installation of the pneumatic connection, 20xx series

→

Screw the plug-in hose connectors onto the Pneumatic Control
Unit and the actuator.

→

Using the hoses supplied in the accessory kit, make the connection
between the Pneumatic Control Unit and the actuator with the fol-
lowing “Tab. 1: Pneumatic connection to actuator”.

note!

damage or malfunction due to ingress of dirt and moisture.

▶ To comply with degree of protection IP65 / IP67, connect the

pilot air outlet which is not required to the free pilot air port of the

actuator or seal with a plug.

“In rest position” means that the pilot valves of the Pneumatic
Control Unit Type 8697 are isolated or not actuated.

If the ambient air is humid, a hose can be connected between
pilot air outlet 2

2

of the Pneumatic Control Unit and the

unconnected pilot air port of the actuator for control function
A or control function B. As a result, the spring chamber of
the actuator is supplied with dry air from the vent duct of the
Pneumatic Control Unit.