Burkert Type 8681 User Manual

Page 9

Advertising
background image

32

Process data

2 static input assemblies
(Input: from the control head to the
DeviceNet Master/Scanner)
1 static output assembly

Inputs

3 discrete feedback signals of the posi-
tion measuring system (pos. S1 - S3)
1 discrete feedback signal of the
external initiators (S4)
1 analog position signal in mm
Supply via DeviceNet string
(11 to 25 V DC)
Switch level high signal

 5 V

Switch level low signal

 1,5 V

Outputs

3 solenoid valves

Power consumption
from the bus:

max. 5 W, (3 valves with each 0,8 W)

Length of the Bus line

11.3.

The maximum total line length (sum of trunk lines and drop
lines) of a network depends on the baud rate.

The maximum total line length (according to DeviceNet
specifi cation) is for:

english

33

Baud rate

Thick Cable

Thin Cable

125

500 m

100 m

250

250 m

100 m

500

100 m

100 m

The maximum drop line length is for:

Baud rate

Drop Line

Sum (in Network)

125

6 m

156 m

250

6 m

78 m

500

6 m

39 m

Electrical Data

11.4.

Electrical power supply:

11 to 25 V DC (according to

specifi

cation)

Max. power consumption: 200 mA at 24 V DC

Input / proximity switches (external initiator: S4 in):
Power supply:

via DeviceNet power

supply - 10 %

Current carrying capacity
sensor power supply:

max. 30 mA

Short-circuit protection
Design:

DC 2- and 3-conductor,

NO contact, PNP output

english

34

Input current 1 signal:

I

Sensor

> 6.5 mA, limited

internally to 10 mA

Input voltage 1 signal:

U

Sensor

> 10 V

Input current 0 signal:

I

Sensor

< 4 mA

Input voltage 0 signal:

U

sensor

< 5 V

Inputs (from master perspective) / binary or analog
feedback signals:
The recovery of the 3 valve positions reported back binarily
or of the analog position signalis described in the manual,
chapter “Position Mesuring System”.

Outputs (from master perspective) / solenoid valves:
max. switching capacity 1.0 W
typ. continuous output

0.8 W

Output reduction

integrated via DeviceNet

interface

electronics

pull-in current

120 mA typ. / 200 ms

(3

valves)

Holding current

100 mA typ. at 24 V DC

(3

valves)

Operating mode

Long-term operation

(100 % operation)

Valve types

6524

Central display of the switching states:
Power consumption from
DeviceNet at 24 V DC

42 mA with 24 V DC power

english

35

supply per illuminated display

shown; Color switching see

in the manual, chapter “LED -

Color

Assignments”

Electrical Installation (DVN)

11.5.

WARNING!

Risk of injury due to electrical shock!

Before reaching into the system (except for the

•

Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety

•

regulations for electrical equipment!

Risk of injury from improper installation!

Installation may be carried out by authorized techni-

•

cians only and with the appropriate tools!

No internal cabling work is required for any of the Devi-
ceNet designs.
However, you will require the correspondingly assembled
cable sets with the pin assignments described below: