Installation

Type 8741

7.6.1 connect the power supply and

communication cable

electrical input assignments:

1 2 3 4

screw terminals,
4-pin
Pin Assignment
1

DGND

2

CAN_L

3

CAN_H

4

24 V

Fig. 12 : Assignment; screw terminals, 4-pin

procedure:

→

Open the protective cover of the MFM/MFC.
On the inside of the protective cover there are engraved symbols
and a support as a stop for assembly of the cable.

Sheath
insulation

Braid

Cable shielding

Support

Fig. 13 : Assembly of the cable for the electrical connection

cable assembly: (See "Fig. 13")

→

Remove the insulation sheath over a length of approx. 25 mm.

→

Shorten the cable shielding to the required length (see engraved
symbols on the inside of the protective cover).

→

Pull back the cable shielding over the insulation sheath.

→

Attach the braid according to the assignment on the screw ter-
minals of the plug connector.

→

To relieve any strain on the cable, secure it to the housing of the
MFC/MFM using a cable tie.

Recess for attaching the
cable tie

Cable tie

Plug connector

Fig. 14 : Attached cable with strain relieved by cable ties